Home / Calculators / Hot Air Generator Calculator
Sizing tool

Size your hot air generator

From air flow or the moisture you need to remove, find the heat load and the Technodry Block model, oil/gas or solid fuel fired.

1What are you drying or heating?
2Margins
3Fuel available at site
₹What you pay for energy

Defaults are indicative. Enter your own rates for an accurate comparison.

Heat load–

Running cost per day

How this is worked out

From air flow: kcal/hr = m³/hr × 1.2 kg/m³ × 0.24 kcal/kg·°C × (T2 − T1).

From moisture: water evaporated = feed × (Mi − Mf) ÷ (100 − Mf) kg/hr, on a wet basis. Heat = water × 650 kcal/kg ÷ dryer efficiency. 650 kcal/kg covers latent heat plus warming the water.

Selection: oil / gas → Technodry Block TDB I / TDB G (150 °C standard, up to 400 °C on request, direct-fired to 800 °C); solid fuel → Technodry Block SF (200 °C). Smallest model at or above load × (1 + losses) × (1 + margin).

Fuel cost at 88 % efficiency for oil / gas and 70 % for solid fuel.

Next step

Want this sizing checked by an engineer?

Your inputs and the recommended model are attached automatically. We will confirm the selection, the accessories and the price.